Fire dampers in Single Skin partitions
Fully tested and supported by comprehensive technical documentation, these innovative details provide a practical answer to the challenges of modern fit-out projects helping you save time on site while delivering the fire performance and regulatory confidence your projects demand.
Key takeaways for fire dampers in single skin partition walls
Rf-Technologies offers one of the most comprehensive ranges of certified fire dampers for single-skin plasterboard partitions, covering both circular (Ø 100 – 630 mm) and rectangular (200 × 100 to 1500 × 1000 mm) models. Tested in the two most common single skin partition types using standard (Type A – 12.5 mm) or fire-rated (Type F – 15 mm) plasterboard, the range combines installation flexibility with reliable fire protection. A universal fire batt sealing method enables fast, clean and dry installation, accommodating openings up to 600 mm larger than the damper dimensions. Certified close-proximity installation allows two dampers within a single builders’ work opening. Dedicated DW145-compliant installation guides are available for each damper model.
Most complete package in the market
Whether designing round or rectangular duct runs, from compact services to high-capacity ventilation paths, Rf-Technologies provides full coverage:
Circular Fire Dampers (CR60, CR2): From Dn 100 up to 630mm.
Rectangular Fire Dampers (CU-LT, CU2): From 200×100 up to 1500×1000 mm.
Tested in two of the most common Single Skin Partition Types
Modern building projects depend on flexible drylining configurations. Our solutions are certified for the two primary single-layer wall specifications:
Standard Plasterboard: 1×12.5 mm either side (typically specified where 30 minutes fire resistance is required).
Fire-Rated Plasterboard: 1×15mm on either side (typically specified where 60 minutes fire resistance is required.)
Single Sealing Method: Fire Batt, one method fits all
The universal fire batt sealing method offers maximum installation flexibility for Rf-Technologies fire dampers. Suitable for both small and large builders’ work openings, accommodating openings up to 600 mm larger than the damper dimensions, this single sealing solution simplifies installation across the entire range. The fast, clean and completely dry installation reduces on-site installation time making the process easier and more efficient for installers.
Two fire dampers at minimal distance, one builders' opening
Rf-Technologies fire dampers are certified for close-proximity installation, allowing two dampers to be installed side by side at minimal distance within a single builders’ work opening. This flexible installation solution reduces the need for additional structural framing and studwork, simplifies on-site installation and helps save valuable installation time.
DOPs, DW145 Technical documentation with installation details
CE and UKCA certified - EN 1366-2 tested
Our fire dampers comply with product standard EN 15650, are tested according to European standard EN 1366-2 and classified according to EN 13501-3. This results in CE-marked and UKCA-compliant products that meet the applicable requirements for fire resistance and integrity under various conditions.
Reaching a full set of CE and UKCA compliant classifications
Rectangular Fire Dampers
| Construction | Classification |
|---|---|
| Plasterboard partition ≥ 75 mm, with single-layer standard plasterboard, 1 × 12.5 mm on either side (Type A to EN 520). | EI 45 (ve i ↔ o) S – (300 Pa) E 60 (ve i ↔ o) S – (300 Pa) |
| Plasterboard partition ≥ 80 mm, with single-layer fire-rated plasterboard, 1 × 15 mm on either side (Type F to EN 520). | EI 60 (ve i ↔ o) S – (300 Pa) E 90 (ve i ↔ o) S – (300 Pa) |
Circular Fire Dampers
| Construction | Classification |
|---|---|
| Plasterboard partition ≥ 75 mm, with single-layer standard plasterboard, 1 × 12.5 mm on either side (Type A to EN 520). | EI 60 (ve i ↔ o) S – (300 Pa) |
| Plasterboard partition ≥ 80 mm, with single-layer fire-rated plasterboard, 1 × 15 mm on either side (Type F to EN 520). | EI 90 (ve i ↔ o) S – (300 Pa) E 120 (ve i ↔ o) S – (300 Pa) |